Telco Envirotrols Inc.

Women's Business Enterprise National Council

 


Specializing in Environmental Equipment, Controls, and Parts


Downloadable Order Form

Home

TEI News Page

Controls Parts

Energy Management

ASI Controls Building Automation

ASI Telco Panel

Bard Wall-Mount and HVAC Equipment

Bard HVAC Parts Supply

Bard Controllers

Nesbitt Equipment

Gas Detection

Environmental Monitors

 

P67 Series

Low Pressure Control

Description

P67 pressure controls are used to close or open an electrical circuit, based on a predetermined air pressure signal.  The operating point of the control and the differential, are easy to adjust with the externally-located adjustment screws on the top of the control enclosure.  The pressure controls incorporate a non-metallic diaphragm that is positioned by air pressure changes.  The diaphragm, in turn, actuates a heavy-duty electrical contact clock using a lever mechanism.

Applications

Typical applications include the control of air compressors, fans, pilot lights, resistance heating elements, and other devices.

Features

  • long-life contact structure with high contact force
  • easy-to-adjust settings: single sight set scales show both cut-in and cut-out settings

Electrical Ratings

P67AA and P67CA

Motor Ratings VAC 1 Phase 2-3 Phase
  120 208 240 277 208 240
AC Full Load Amp 12.0 12.0 12.0 - 12.0 12.0
AC Locked Rotor Amp 72.0 72.0 72.0 - 72.0 72.0
AC Non-Inductive Amp 12.0 12.0 12.0 12.0 - -
DC Non-Inductive Amp 3.0 0.5 0.5 - - -
Pilot Duty - 125 VA, 120 to 600 VAC; 57.5 VA, 120 to 300 VDC

P67EA and P67FA

Pole Number Line-M2 (Main) Line-M1 (Auxiliary)
Motor Ratings VAC 120 208 240 277 120 208 240 277
AC Full Load Amp 16.0 9.2 8.0 - 6.0 3.3 3.0 -
AC Locked Rotor Amp 96.0 55.2 48.0 - 36.0 19.8 18.0 -
AC Non-Inductive Amp 16.0 9.2 8.0 7.2 6.0 6.0 6.0 6.0
Pilot Duty: 125 VA, 120 to 600 VAC; 57.5 VA, 120 to 300 VDC

Selection Chart

Code Number Control Action Scale Range psig1 (kPa) Temperature Range Differential psig (kPa) Max Over-Pressure psig (kPa) Connector
P67AA-1C DPST opens on pressure drop 3 to 30

(21 to 207)

32 to 140°F

0 to 60°C

1 1/2-20 (10 to 138) Adjustable 50 (345) Angie Barbed Fitting
P67CA-1C DPST opens on pressure rise
P67EA-5C L-M2 contacts connect on pressure rise and simultaneously the L-M1 contacts break 1/8 in. Male NPT

1.    Range is minimum cut-out to maximum cut-in on Open Low controls.  It is minimum cut-in to maximum cut-out on Open High controls.