Description

The P47 controls are available with SPST, DPST, or 4-wire, two-circuit contacts for line voltage or low voltage.  The pressure connector is 1/4 in. male NPT (0-15 psig only) or 1/4 in. female NPT (for all other ranges).

Applications

P47 steam pressure controls are designed for high limit or operating control applications.  A typical use is as a limit control on steam heating systems.  Models that close on a pressure increase are used on steam unit heaters to avoid blower operation when steam pressure is below the point required for adequate heating.  The P47 can be used with steam, water, air, or noncombustible gases that do not harm iron or copper.

Features

  • long-life contact structure with high contact force
  • easy-to-adjust single sight set scales show both cut-in and cut-out settings
  • compact size
  • trip-free manual reset

Accessories

The Part No. TBG16A-600R Siphon is supplied with all controls except models with 0 to 15 psig range.

Electrical Ratings

P47AA and P47BA

Motor Ratings VAC 120 208 240 277
AC Full Load Amp 16.0 9.2 8.0 -
AC Locked Rotor Amp 96.0 55.2 48.0 -
AC Non-Inductive Amp 16.0 16.0 16.0 16.0
Pilot Duty - 125VA, 120 to 600 VAC; 57.5 VA, 120 to 300 VDC

P47GA

Pole Number Line-M2 (Main) Line-M1 (Auxiliary)
Motor Ratings VAC 120 208 240 277 120 208 240 277
AC Full Load Amp 16.0 9.2 8.0 - 6.0 3.3 3.0 -
AC Locked Rotor Amp 96.0 55.2 48.0 - 36.0 19.8 18.0 -
AC Non-Inductive Amp 16.0 9.2 8.0 7.2 6.0 6.0 6.0 6.0
Pilot Duty: Both Poles 125 VA, 120 to 600 VAC; 57.5 VA, 120 to 300 VDC

Selection Chart

Code Number Number of Poles Range psig (kPa) Differential psig (kPa) Max Over-Pressure psig (kPa)
Min Max
Contacts Open On Rise  Automatic Reset
P47AA-1C 1 0 to 15 (0 to 103) 2 (14) 8 (55) 50 (345)
P47AA-4C 1 20 in. Hg to 50

 (-68 to 345)

5 (34) 35 (241) 180 (1241)
P47AA-13C 1 0 to 150 (0 to 1034) 12 (83) 50 (345) 325 (2241)
Contacts Close On Rise  Automatic Reset
P47BA-1C 1 0 to 15 (0 to 103) 2 (14) 8 (55) 50 (345)
P47BA-6C 1 0 to 150 (0 to 1034) 12 (83) 50 (345) 325 (2241)
4-Wire Two CircuitAutomatic Reset
P47GA-9C1 Main Open High; Auxiliary Open Low 0 to 150 (0 to 1034) 12 (83) 50 (345) 325 (2241)

1.    The main contacts (Line-M2) open on rise, as the auxiliary contacts (Line-M1) close.