P29 Series Low Pressure Control (With Time Delay) Description P29NC is a low pressure control with time delay and lockout, which requires manual reset. A drop in pressure energizes the time delay relay and opens a contact after 60 seconds, shutting down the equipment. The time delay prevents nuisance shutdowns due to momentary fluctuations in system pressures. Applications
Features
Accessories
Technical Specifications
Selection Chart
Example: Setpoint @ 10 psig. On a rise in pressure the timing circuit opens at 10 psig and time out ends. On a fall in pressure the timing circuit energize at 6-9 psig and the time out begins. If the pressure fails to reach 10 psig within the 60 second time delay, the main contacts open shutting down the controlled equipment. |