ND-1
Nitrogen
Dioxide Transducer and Meter
- Diesel Exhaust detection and
control
- Meets OSHA and State of
Wisconsin Requirements
- SPDT Fan Relay, adjustable
from 0.5 to 3.0 ppm of Nitrogen Dioxide
- N.O. Alarm Relay, adjustable
from 1.0 to 5.0 ppm of Nitrogen Dioxide
- Highly Linear Electro-Chemical
Sensor
- Digital display, 0 – 9 ppm of
Nitrogen Dioxide
Features:
- General Guideline on spacing:
5000 sq. ft. per unit
- Locate detector 4 to 5 feet
above floor
- Specific to Nitrogen Dioxide
- Internal adjustment setpoints
for fan and alarm systems
- The ND-1 is housed in a UL
knockout box, facilitating installation and hook-up
- Low Voltage Operation - Power
input 24 VDC or 24 VAC
- Field Calibration Kit
(ND1-FCK) is available
- Supervised Electro-Chemical
Sensor
|
Specifications: |
|
Power |
1.2 watts (12 to 24 VAC or VDC) |
|
Range |
0 - 9 ppm of Nitrogen Dioxide |
|
Operating Environment |
0 to 125°F, 10 to 90% RH |
|
Fan Relay |
SPDT, 5 Amps, 240 Volts |
|
Fan Relay Setpoint/Delay |
0.5 to 3.0 ppm / 0.5 to 5
minutes |
|
Alarm Relay |
N.O., 0.5 Amps, 200V, 10VA |
|
Alarm Relay Setpoint |
1.0 to 5.0 ppm |
|
Accuracy (after calibration) |
±3% |
|
Linearity |
±1% |
|
Size |
6x6x3 inches |
|
Shipping Weight |
3 pounds |
|
Color/Enclosure Rating |
Gray/NEMA 1 |
|