GT-11
Methane/LP Combustible Gases
- Dual linear output transducer:
unit sends either a 4 to 20 milliamp or 1 to 5 volt signal.
- The standard calibration for
the GT-11 is to the following range: 0 to 10,000 ppm of methane. 10,00 PPM is
approximately 20%of the Lower Explosive Limit of methane.
- Easy installation: unit is low
voltage (24 VAC or VDC) and mounts nearly flush to the wall in a standard 4 x
4 electrical box. Optional duct mounting kits are available.
- Dual operating LED lights: the
green LED indicates normal operating condition and the amber LED indicates a
trouble condition.
- Supervised System: unit
continually checks itself and indicates a trouble condition if there is ever a
failure of the sensor or circuitry.
- Standard calibration detects
the following gases: Methane, LP, gasoline fumes, butane, acetylene, and
propane.
- Special calibrations are
available for the GT-11 to detect other gases including: jet fuel,
alcohol, ethane, ethylene oxide, kerosene fumes, etc.
- Low maintenance self-purging
semiconductor sensor.
|