F62 Series

Airflow Switch (SPDT - contact Unit)

Description

This control detects air flow or the absence of air flow in ducts, responding only to the velocity of air movement.  The one-piece stainless steel paddle can be trimmed, if necessary.  The control is supplied with mounting plate gasket.

The range adjusting screw permits field adjustment of flow rate setting.

Applications

A typical application includes air flow sensing in make-up air and exhaust systems.

Features

  • rugged steel enclosure
  • easy access to wiring terminals

Electrical Ratings

Motor Ratings VAC 120VAC 208VAC 240VAC 277VAC
Nominal Horsepower 1 1 1 -
AC Full Load Amp 16.0 8.8 8.0 -
AC Locked Rotor Amp 96.0 52.8 48.0 -
Non-Inductive or Resistance Load Amp 22.01 22.01 22.01 22.01
Pilot Duty - 125 VA, 120/277VAC

1.    SPST normally closed or normally open rating, SPDT rating is 16.0 amp

Air Velocity Required to Actuate Switch

Paddle Width (in.) Switch Actuation on Flow Minimum Air Velocity in FPM (m/sec) Required to Actuate Control1
Horizontal Flow Vertical Flow (Upward)
50 in2 (323 cm2) or Larger Duct Area Less than 50 in2(323 cm2) Duct Area 50 in2 (323 cm2) or Larger Duct Area Less than 50 in2(323 cm2) Duct Area
2-1/8 Increase (R to Y Closes) 625 (3.2) 575 (2.9) 950 (4.8) 750 (3.8)
Decreases (R to B Closes) 325 (1.7) 220 (1.1) 850 (4.3) 575 (2.9)
3-1/8 Increase (R to Y Closes) 500 (2.5) 350 (1.8) 750 (3.8) 500 (2.5)
Decreases (R to B Closes) 250 (1.3) 100 (0.5) 650 (3.3) 350 (1.8)

1.    These are only approximations.  Actual trip points are affected by air turbulence, humidity, air density, air temperature, and other factors.

Selection Charts

Code Number Paddle Size in. Dimension Maximum Ambient Temp, °F (°C) Max. Air Velocity
F62AA-8C1 2-1/8 in. x 6-7/8 in. 10-3/8in. H (including paddle), 4 in. W, 2-13/16 in. D 100 (40) 2000 FPM (10m/sec)
F62AA-9C 3-1/8 in. x 6-7/8 in. 10-3/8in. H (including paddle), 4 in. W, 2-13/16 in. D 100 (40) 2000 FPM (10m/sec)

1.    Replaces McDonnell Miller AF-2.