DATApro Multi-Purpose Recording Meter

The DATApro series can monitor, store and analyze data from a variety of common sensors, allowing you to make the right decision for your application.  A growing family of DATApro models is available to meet almost any measuring need.  Virtually any utility - gas, water, electric, steam, HVAC, compressed air, solid or liquid waste - can be recorded.

Versatile Options 

  • Modem - For long-term monitoring applications an internal modem is available.  The modem can be programmed to automatically download data or used to read real-time values.
  • Weatherproof - A custom housing is dust and liquid resistant, allowing the unit to operate in harsh, wet and outdoor environments.
  • High Memory - This is the option you want when recording lots of data.  Capacity is quadrupled to store up to 100,000 records between downloads.

 

DATApro Power Meter Specifications

Inputs 4 channels of AC current, DC voltage, DC milliamps, pulse count, or temperature
Measurements Minimum, Maximum, Average, Total
Frequency 10 Hz (pulse) and 50 or 60 Hz (current)
Accuracy <1% of reading, exclusive of sensor accuracy
Baud Rate Up to 57,600 (direct) or 14,400 (modem)
Resolution Better than .1% FS for all parameters; 12 bit A/D (1 part in 4, 096)
Memory 128kB (25,000 readings) or 512kB (100,000 readings)
Sampling Frequency 7.68 KHz (128 points per current waveform) or 10 Hz, interrupt driven
Recording Intervals 3, 15, 30 seconds; 1, 2, 5, 0, 15, 20, 30 minutes and 1, 12, 24 hours
Real Time Clock Crystal controlled, true calendar, 20 ppm accuracy (<1min/month)
Battery Life 3 years at 1 minute sampling, LED indicator of low batter
Operating Temperature - 7 to 60°C (20 to 140°F)
Operating Humidity 5% to 95% non-condensing
Dimensions 8x15x6cm  (3.2"x5.9"x2.4")
Weight 340gm (12 ounces)

For pricing, please call 302-846-9103.