Accustat L V Series Single Stage Line Voltage Controls

Description:

ACCUSTAT® Line Voltage temperature controls can save you up to 15% in energy over bi-metal and vapor tension line voltage thermostats, that are slow to temperature change and have wide differential.  ACCUSTAT® with its snap-in preset sensors have inherent advantages such as, greater accuracy, no temperature drift, and near "0" droop.  Locking covers, along with preset sensors, allow for a tamper-resistant design.  Models for either 120 or 220 volts with 1 amp, 5 amps, or 20 amps load ratings.

Application:

Line voltage single stage heat and heat/cool applications, ventilating fans, baseboard heaters, fan coil units, etc.  Especially effective where thermostat tampering is a problem.  The high accuracy and efficiency of these units makes them "automatic upgrades" for bimetal or gas bulb type line voltage thermostats.

Specifications:

Voltage

120 or 220 VAC

Sensing

Preset or adjustable sensors

Rating

1, 5 or 20 amps, depending on model
Stages Single Stage
Differential Approx. 2°F depending on air flow and load
Case Plastic, white
Locking Case Special key required
Wire Connections Wire with wire nuts
Dimensions 4.7Wx4.7Hx1.8D

 

Model Information:
Model Function/ Stages Sensors Required Voltage/Load Switches
LV120-H1 HT Only 1 120VAC/1 Amp Off/On
LV120A-h1 1 HT 1 120VAC/20 Amps Off/On
LV120B-H1 1 HT 1 120VAC/5 Amps Off/On
LV120-H2 1 HT

(2 temp settings)

2 120VAC/1 Amp Off/On; Lo/Hi
LV220A-H1 1 HT 1 220VAC/20Amps Off/On
LV120-AH11 1CL/1HT 2 120VAC/1 Amp Off/On; HT/CL
LV120B-AH11 1CL/1HT 2 120VAC/5 Amps Off/On; HT/CL
LV120B-AH22    1CL/1 HT        (2 temp settings) 4 120VAC/5 Amps Off/On; HT/CL; Lo/Hi

 

Engineering Specifications:

Thermostats shall be 120 or 220 volt heating or heating/cooling type, rated at either 1 or 5 amps, as specified.  Temperature sensing shall be by means of hermetically sealed snap-in mercury sensors with preset temperature settings.  Sensor shall be actuated by the mercury column containing internal platinum electrodes.  Case shall be molded plastic and have an integral locking cover.

 

Warranty:

PSG Controls carry a "limited 1 year warranty" against defects in workmanship and materials (contact PSG for full warranty policy).