A70 Series

Four-Wire, Two-Circuit Temperature Control

Description

The A70 Series temperature control incorporates a vapor-charged sensing element.  The A70G, A70H, and A70K have a 4-wire, 2-circuit contact block that contains two isolated sets of contacts.

The contacts are designed so that when the main contact opens, the auxiliary contact closes.

Applications

Typical applications include energizing an indicator light after a low temperature cutout on a ventilating system.

Features

  • ling life, snap-acting contacts
  • automatic or manual reset models

Replacement Covers

Code Number Description
CVR17A-620R Automatic Reset Cover
CVR17A-621R Manual Reset Cover

Electrical Ratings

Pole Number LINE-M2 (Main Line-M1 (Auxiliary)
Motor Ratings VAC 120 208 240 277 4801 6001 120 208 240 277
AC Full Load Amp 16.0 9.2 8.0 - 5.0 4.8 6.0 3.4 3.0 -
AC Locked Rotor Amp 96.0 55.2 48.0 - 30.0 28.8 36.0 20.4 18.0 -
AC Non-Inductive Amp 16.0 9.2 8.0 7.2 - - 6.0 6.0 6.0 6.0
Pilot Duty - Both Poles 125VA, 120 to 600 VAC and 57.5 VA, 120 to 300 VDC

1.    Not compressor motor loads.

Selection Chart

A70 Series Four-Wire, Two-Circuit Temperature Control

Code Number Switch Action Range F (C) Diff F (C) Bulb and Capillary Max Bulb Temp F (C) Range Adjuster
Main Contacts Auxiliary Contacts
A70GA-1C1 Open Low Close Low 15 to 55

(-9.4 to 12.8)

5 (2.8) 20 ft. of 1/8 in. O.D. Tubing 400 (204.4) Screwdriver Slot
A70GA-2C Open Low Close Low 35 to 80

 (1.7 to 26.7)

3 to 3.0 (-16.1 to -1.1) factory set at 12 (-11.1) 3/8 in. x 3 in., 6 ft. Cap 250 (121) Screwdriver Slot
A70HA-1C1 Open Low Close Low 15 to 55 

(-9.4 to 12.8)

Manual Reset 20 ft. of 1/8 in. O.D. Tubing 400 (204.4) Screwdriver Slot
A70HA-2C Open Low Close Low 35 to 80

(1.7 to 26.7)

Manual Reset 3/8 in. x 3 in., 6 ft. Cap 250 (121) Screwdriver Slot
A70KA-1C Open High Close High 100 to 170 (37.8 to 76.7) Manual Reset 3/8 in. x 3 in., 6 ft. Cap 240 (116) Screwdriver Slot

1. The low cutout stop is set and sealed at 35°F (1.6°C)  The control responds only to the lowest temperature along any one ft. of the entire 20 ft.  element or bellows cup.