A36 Series
Four Stage Remote Bulb
Thermostats
Description
The A36 eries are four stage thermostats with open
construction for use in panel mounting.
Applications
Use for cycling control for multiple refrigeration
compressors or unloading type compressors.
Features
Screwdriver slot adjustment with calibrated dial enables
movement of entire staging band within the range.
Accessories
Order Enclosure CSE57A-600 separately, if required.
Specifications
Maximum bulb temperature is 120°F (49°C) in operation and
140°F (60°C) when shipping.
Electrical Ratings
|
Motor Ratings VAC |
120 |
208 |
240 |
277 |
|
A36AHA |
|
AC Full Load Amp |
10.0 |
6.9 |
5.0 |
- |
|
AC Locked Rotor Amp |
60.0 |
41.4 |
30.0 |
- |
|
Non-Inductive Amp |
16.0 |
9.2 |
8.0 |
7.2 |
|
Pilot Duty - 125 VA, 120/277 VAC |
|
A36AHB |
|
AC Full Load Amp |
6.0 |
3.4 |
3.0 |
- |
|
AC Locked Rotor Amp |
36.0 |
20.4 |
18.0 |
- |
|
Non-Inductive Amp |
0 |
5.7 |
5.0 |
4.3 |
|
Pilot Duty - 125 VA, 120/277 VAC |
Selection Chart
|
Code Number |
Switch Action |
Range F (C) |
Diff F (C) |
Bulb and Capillary |
Bulb Well No. (order separately) |
Range Adjuster |
|
A36AHA-50C1 |
4-SPDT Switches |
55 to 95 (13 to 35) |
2 Ea. Stage 1 1/2 (0.8)
Between Stages |
3/8 in. x 5 1/4 in. 18 in. Cap w/12 in. Nylon Armor |
WEL14A-603R |
Screwdriver Slot with Calibrated Dial |
|
A36AHA-52C1 |
4-SPDT Switches |
55 to 95 (13 to 35) |
2 Ea. Stage 1 1/2 (0.8)
Between Stages |
3/8 in. x 5 1/4 in. 18 in. Cap w/12 in. Nylon Armor |
WEL14A-603R |
Screwdriver Slot with Calibrated Dial |
|
A36AHA-58C2 |
4-SPDT Switches |
0 to 70 (-18 to 21) |
3 Ea. Stage 2 1/2 (1.4)
Between Stages |
3/8 in. x 4 3/4 in. 15 ft. Braid Armor Cap |
WEL14A-602R |
Screwdriver Slot with Calibrated Dial |
|
A36AHB-33C1 |
4-SPDT Switches |
0 to 70 (-18 to 21) |
2 Ea. Stage 2 1/2 (1.4)
Between Stages |
3/8 in. x 4 3/4 in. 15 ft. Braid Armor Cap |
WEL14A-602R |
Screwdriver Slot with Calibrated Dial |
1. Calibrated at mid-switching
point...computer room or comfort control.
2. Calibrated at low-switching
point...special close control chiller applications.
|