A28 Series

Two Stage Flange Mounted Duct Thermostat

Description

The A28AK is a two stage temperature control with special air coil sensing element and adjustable mounting flange. 

Applications

These duct thermostats are used on roof top units, make-up heaters, duct heaters, and air handling systems of all types.

Features

  • flat flange mounting with special coil element permits positioning of sensing bulb in the appropriate portion of the air stream
  • 2 SPDT snap acting switches
  • unaffected by barometric pressure or cross ambient temperatures

Electrical Ratings

Motor Ratings VAC 120 208 240 277
AC Full Load Amp 6.0 3.4 3.0 -
AC Locked Rotor Amp 36.0 20.4 18.0 -
Non-Inductive or Resistance Load Amps (Not Lamp Loads) 10.0 9.2 8.0 7.2
Pilot Duty - 125 VA, 24 to 277VAC

Note:      When used as two circuit control, the total connected load must not exceed 2000VA.

Selection Chart

Code Number Number of Stages Switch Action Range F (C) Maximum Allowable Temperature at Bulb F (C)
Each Stage Between Stage
A28AK-1C 2 2-SPDT Switches 2 (1.1) 3 (1.7) 140 (60)
A28AK-2C 2 2-SPDT Switches

 

2 (1.1) 3 (1.7) 200 (93)